Ld0.Cmmxu1 Three-Phase Current Measurement (1); Ld0.Csmsqi1 Sequence Current Measurement (1); Ld0.Mdsopt1 Runtime Counter For Machines And Devices (1) - ABB RELION 611 Series Modbus Point List Manual

Motor protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757464 C
RegA
Type
Scale
u16
1000
u16
1000
u16
1000
2.4.1.29
Table 71:

LD0.CMMXU1 Three-phase current measurement (1)

RegA
Type
Scale
138
u16
1000
139
u16
1000
140
u16
1000
2.4.1.30
Table 72:

LD0.CSMSQI1 Sequence current measurement (1)

RegA
Type
Scale
143
u16
1000
144
u16
1000
145
u16
1000
2.4.1.31
Table 73:

LD0.MDSOPT1 Runtime counter for machines and devices (1)

RegA
Type
Scale
2048
u16
1
REM611
Point List Manual
IEC 61850 name
.A.phsA.cVal.mag.f
.A.phsB.cVal.mag.f
.A.phsC.cVal.mag.f
LD0.CMMXU1 Three-phase current measurement (1)
IEC 61850 name
LD0.CMMXU1
.A.phsA.instCVal.mag.f
.A.phsB.instCVal.mag.f
.A.phsC.instCVal.mag.f
LD0.CSMSQI1 Sequence current measurement (1)
IEC 61850 name
LD0.CSMSQI1
.SeqA.c1.instCVal.mag.f
.SeqA.c2.instCVal.mag.f
.SeqA.c3.instCVal.mag.f
LD0.MDSOPT1 Runtime counter for machines and devices (1)
Since the register size is 16 bits, the value saturates at 65535 hours (approximately 7.5
years). Alternatively, a 32-bit user-definable register can be made of this data to cover
the whole 300 000 hours (34 years) range. The value can also, for example, be rescaled
to show "total operation days" instead by changing the scale factor from 1 to 1/24 =
0.0417.
IEC 61850 name
LD0.MDSOPT1
.OpTmh.stVal
SA name
Description
Max demand IL1
Phs A amplitude
Max demand IL2
Phs B amplitude
Max demand IL3
Phs C amplitude
SA name
Description
Phase current (1)
I_INST_A
Phs A amplitude
I_INST_B
Phs B amplitude
I_INST_C
Phs C amplitude
SA name
Description
Sequence of currents
I1_INST
Positive amplitude
I2_INST
Negative amplitude
I3_INST
Zero amplitude
SA name
Description
OPR_TIME
Total operation hours
Section 2
Modbus data mappings
Values
0.00...50.0
[×In]
0.00...50.0
[×In]
0.00...50.0
[×In]
Values
0.00...40.0
[×In]
0.00...40.0
[×In]
0.00...40.0
[×In]
Values
0.00...40.0
[×In]
0.00...40.0
[×In]
0.00...40.0
[×In]
Values
0..299999
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rem611

Table of Contents