Ctrl.cbcswi1 Circuit Breaker Control (1); Ld0.Ldev1 Protection Relay's Warm Reset (1); Unmapped Control Points - ABB RELION 611 Series Modbus Point List Manual

Motor protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 2
Modbus data mappings
0xA
CS
2069
2.09
2073
2.13
2.5.2
Table 80:

CTRL.CBCSWI1 Circuit breaker control (1)

0xA
CS
2048
1.00
2049
1.01
2050
1.02
2051
1.03
2052
1.04
2053
1.05
2.5.3
Table 81:

LD0.LDEV1 Protection relay's warm reset (1)

0xA
CS
2080
3.00
2.5.4
50
IEC 61850 name
.RcdRs.Oper.ctlVal
LD0.RESCMMXU1
.RcdRs.Oper.ctlVal
CTRL.CBCSWI1 Circuit breaker control (1)
IEC 61850 name
CTRL.CBCSWI1
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
.Pos.Oper.ctlVal
LD0.LDEV1 Protection relay's warm reset (1)
IEC 61850 name
LD0.LDEV1
.WrmStrCmd.Oper.ctlVal

Unmapped control points

Table 82:
Unmapped control points
IEC 61850 name
LD0.LLN0
.MeasStatRs.Oper.ctlVal
LD0.FLTRFRC1
.RcdRs.Oper.ctlVal
SA name
Description
Reset Max current1 demands
Reset Io (1) max demands
SA name
Description
Select open
Select close
Cancel selection
Execute selection
Direct open
Direct close
SA name
Description
Warm reboot of protection relay
Description
Reset all min. and max. demands
Reset fault record data
1MRS757464 C
Values
1=Reset
1=Reset
Values
1=Select
1=Select
1=Cancel
1=Execute
1=Open
1=Close
Values
1=Reboot
Value
1=Reset
1=Reset
REM611
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for: