CTRL.LLN0 Local, Remote, Station, Off and Combinations

RegA
Type
u16
2.5
2.5.1
Table 79:

Reset, acknowledge and trigger points

0xA
CS
2060
2.00
2061
2.01
2067
2.07
2068
2.08
Table continues on next page
REM611
Point List Manual

Unmapped registers

Unmapped registers are register data that have no initial Modbus mapping locations,
but can be added to the user-definable Modbus area using the Communication
Management tool in PCM600. The initial register type settings of these objects have
little meaning, since it is always possible to redefine the settings completely for the
user-definable register.
CTRL.LLN0 Local, Remote, Station, Off and Combinations
Scale
IEC 61850 name
CTRL.LLN0
1
.LocKeyHMI.stVal

Controls

Table 78:
Explanations of the controls table columns
Column name
Description
0xA
Coil (0X) address for control value.
CS
Control structure and bit within the structure for control value.
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as Logical
name
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the written value.
Reset, acknowledge and trigger points
IEC 61850 name
LD0.LLN0
.IndLEDRs.Oper.ctlVal
.ProgLEDRs.Oper.ctlVal
DR.RDRE1
.RcdTrg.Oper.ctlVal
.MemClr.Oper.ctlVal
LD0.CMMXU1
SA name
Description
0=Off; 1=Loc; 2=Rem; 3=Stat;
4=L+R; 5=L+S; 6=L+S+R; 7=S
+R
SA name
Description
Reset indications and LEDs
Reset Alarm LEDs
Trig DR recording
Clear DR memory
Section 2
Modbus data mappings
Values
0...7
Values
1=Reset
1=Reset
1=Trig
1=Clear
49