INPUTS/OUTPUTS menu - Anti-freeze resistance and compressor phases alarm digital outputs
Visualisation on unit display
A
Input/Output
B
Master digital output
C
07= Antifreeze heater:
D
08= ASerius alarm:
INPUTS/OUTPUTS menu - Evaporator pump digital outputs
Visualisation on unit display
A
Input/Output
B
Master digital output
C
09= Evaporator pump 1:
Visualisation on unit display
A
Input/Output
B
Master digital output
C
10= Liquid solenoid 1:
D
11= Liquid solenoid 2:
Visualisation on unit display
A
Input/Output
B
Master digital output
C
12= 4Way valve circ.1:
D
13= 4Way valve circ.2:
Index
Close
Open
Index
Open
INPUTS/OUTPUTS menu - Solenoid valves digital outputs
Index
C/D
Close
---
INPUTS/OUTPUTS menu - 4-way valves digital outputs
Index
C/D
Open
---
Display/Parameter
A
Inputs/Outputs: Indicates the state of the different entries/exits.
B
Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C
07: indicates the status of the digital output linked to the anti-freeze
resistance. The status of this output can be one of the following:
• Closed = normal functioning
• Open = Anti-freeze alarm active;
D
08: indicates the status of the digital output linked to the compressor
phases alarm. The status of this output can be one of the following:
• Closed = compressor phases alarm in progress;
• Open = no alarm in progress;
Display/Parameter
A
Inputs/Outputs: Indicates the state of the different entries/exits.
B
Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C
09: indicates the status of the pump indicated, the status of
this output can be one of the following:
• Closed = pump ON;
• Open = pump OFF;
Display/Parameter
A
Inputs/Outputs: Indicates the state of the different entries/exits.
B
Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
10-11: indicates the status of the solenoid valves indicated,
the status of this output can be one of the following:
• Closed = valve ON;
• Open =valve OFF;
• --- = valve not present;
Display/Parameter
A
Inputs/Outputs: Indicates the state of the different entries/exits.
B
Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
12-13: indicates the status of the 4-way valves indicated, the
status of this output can be one of the following:
• Closed = valve ON;
• Open =valve OFF;
• --- = valve not present;