INPUTS/OUTPUTS menu - Compressor magnet circuit breaker flow switch digital inputs
Visualisation on unit display
A
Input/Output
B
Master digital input
C
05= Evap.water flow:
D
06= Ovrl.cmp.1 circ.1:
INPUTS/OUTPUTS menu - Compressor 2 magnet circuit breaker digital inputs and compressor phases
Visualisation on unit display
A
Input/Output
B
Master digital input
C
07= Ovrl.cmp.2 circ.1
D
08= Serious alarm:
INPUTS/OUTPUTS menu - HIGH/LOW pressure pressure switch status digital inputs (circuit 2)
Visualisation on unit display
A
Input/Output
B
Master digital input
C
09= High press.circ.2:
D
10= Low press.circ.2:
48
Index
A
B
C
Close
D
Close
Index
A
B
C
Close
D
Close
Index
A
B
C
Close
Close
D
Display/Parameter
Inputs/Outputs: Indicates the state of the different entries/exits.
Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
05: indicates the status of the flow switch positioned on the
evaporator, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = minimum water flow rate threshold exceeded at the
evaporator (Flow switch alarm);
06: indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
Display/Parameter
Inputs/Outputs: Indicates the state of the different entries/exits.
Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
07: indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
08: indicates the status of the phase control on the compres-
sors, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = incorrect phases detected on the compressor indi-
cated (Serious alarm);
Display/Parameter
Inputs/Outputs: Indicates the state of the different entries/
exits.
Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
01: indicates the status of the high pressure switch, mounted
on the cooling circuit indicated. The status of this component
can be one of the following:
• Closed = normal working state;
• Open = maximum pressure threshold exceeded
(HIGH PRESSURE alarm);
02: indicates the status of the low pressure switch, mounted
on the cooling circuit indicated. The status of this component
can be one of the following:
• Closed = normal working state;
• Open = minimum pressure threshold exceeded
(LOW PRESSURE alarm);