▶ Following screen is displayed when Alarm Type is set to AH.F & DO.FS at [Figure 9-3 Alarm Signal Setup
Screen-2].
① Set Alarm Set Point.
② Set hysteresis applied for Alarm Operation.
③ Alarm Signal sends the actual alarm after preset Delay Time when the alarm condition is satisfied.
④ Set High Deviation Limit for Deviation Alarm.
⑤ Set Low Deviation Limit for Deviation Alarm.
Table 9-2 Alarm Signal Setup Screen-2 Parameter
Parameter
Alarm #n Type
Alarm #n POINT
Alarm #n High POINT
Alarm #n Low POINT
Alarm #n Hysteresis
Alarm #n Delay Time
* #n : 1 ~ 4
2nd Edition of TEMP2000_Series IM : July. 16. 2010
[Figure 9-4] Alarm Signal Setup Screen-2/3
Range
OFF, AH.F, AL.F, DH.F
DL.F, DH.R, DL.R
DO.F, DI.F, AH.R
AL.R, AH.FS, AL.FS
DH.FS, DL.FS, DH.RS
DL.RS, DO.FS, DI.FS
AH.RS, AL.RS
EU(-5.0~105.0%)
EUS(-100.0~100.0%)
EUS(0.0~100.0%)
0.00~99.59 (MIN.SEC)
Unit
Default
ABS
EU(100.0%)
EU
(Alarm #n Type are not
DO.F, DI.F, DO.FS, DI.FS)
EUS(0.0%)
EUS
(Alarm #n Type = DO.F,
EUS
DI.F, DO.FS, DI.FS)
EUS
EUS(0.5%)
ABS
00.00
OFF