7.2 Inner Signal Operation
▶ By setup the Slope from Fix Operation, "TSP(Target Setting Point)" works same as "TSP" in Program
Control. But "TSP" work as "Setting Point(SP)" if the change ratio is not set.
Setup
▶ Input = 0.0 ~ 100.0
→ EUS 0.5% = 0.5
▶ Operation Type = Pattern
▶ TYPE = Target Value(PV)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band =In Band
(INB)
▶ Delay Time = 00.00
▶ Input = 0.0 ~ 100.0
→ EUS 0.5% = 0.5
▶ Operation Type = Pattern
▶ TYPE = Target Value (PV)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band = Outside
Band (OUTB)
▶ Delay Time = 00.00
▶ Input = 0.0 ~ 100.0
▶ Operation Type = Pattern
▶ TYPE = Set Point(SP)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band =In Band
(INB)
▶ Delay Time = 00.10
▶ Input = 0.0 ~ 100.0
▶ Operation Type = Pattern
▶ TYPE=Target Set Point
(TSP)
▶ Range Low = 30.0%
▶ Range High = 50.0%
▶ Oper. Band = Outside
Band (OUTB)
▶ Delay Time = 00.00
2nd Edition of TEMP2000_Series IM : July. 16. 2010
SEG1
HYS
50.5
50.0
30.0
HYS
29.5
ON
IS
OFF
SEG1
HYS
49.5
50.0
30.0
HYS
30.5
ON
IS
OFF
SEG1
50.0
30.0
ON
IS
OFF
SEG1
50.0
30.0
ON
IS
OFF
Inner Signal Operation
SEG2
SEG3
SEG4
PV
SEG2
SEG3
SEG4
PV
SEG2
SEG3
SEG4
SP
DELAY TIME
SEG2
SEG3
SEG4
SP
SEG5
INB
SEG5
OUTB
OUTB
SEG5
INB
SEG5
OUTB
OUTB