Up, Soak, Down Signal Operation - Samwontech TEMP2000 Series Installation Manual

Hide thumbs Also See for TEMP2000 Series:
Table of Contents

Advertisement

SAMWONTECH

5.2 UP, SOAK, DOWN Signal Operation

▶ Input Sensor = Temperature(K2), Range = -200.00℃ ~ 1370.00℃
▶ Up, Down Signal Range → [EUS 0% ~ EUS 10% ] = [ 0.00 ℃ ~ 20.00 ℃ ]
Setup
Operation Type
→ Pattern Operation
▶ Up Temperature
→ 0.2 ℃
▶ Soak Temperature
→ 2 Minute
▶ Down Temperature
→ 0.2 ℃
▶ Fix Operation
Do not use
Change Rate
Operation
Operation Type
→ Fix Operation
▶ Up Temperature
→ 0.2 ℃
▶ Soak Temperature
→ 2 Minute
▶ Down Temperature
→ 0.2 ℃
▶ Fix Operation
Do not use
Change Rate
Operation.
☞ Soak Signal Relay
does not become
ON for Fix
Operation. Only
Status Lamp is ON
at operation
screen.
2nd Edition of TEMP2000_Series IM : July. 16. 2010
Up, Soak, Down Relay Operation according to Set Value
Up
50.0℃
49.8℃
30.2℃
30.0℃
Temp. Up
ON
Relay Output
Temp. Soak
Relay Output
Temp. Down
Relay Output
50.0℃
49.8℃
30.2℃
30.0℃
Temp. Up
ON
Relay Output
Temp. Soak
Lamp Display
Temp. Down
Relay Output
Soak
Set Point(SP)
Down Temperature Set
Soak Set Time
2 Minute
ON
Set Point(SP)
Down Temperature Set
ON
Down
Soak
Up Temperature Set
ON
ON
Up Temperature Set
Set Point(SP)
ON
ON
Page 50 / 87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Temp2500Temp2700

Table of Contents