The
units are designed for the
function of the specific needs of the system which they are intended for. Their only serial element is the construction system, while their
technical performance characteristics are customized and specified in the annexed documents such as specification data sheets, layouts,
electric diagrams, etc. that are their integrating parts.
SABIANA
bears neither responsibilities nor bounds, of any kind, for any use different from the one specified above.
Particular attention shall be paid when choosing the installation place of the
atmosphere in which it is installed must not be explosive or corrosive for the materials which build up the unit.
The careful reading of this manual permits to carry out the correct installation, precise setup and effective maintenance. together with its
annexes, the manual shall be kept with care and made available for every reference.
All the installation, test and servicing operations must be carried out by qualified personnel, that is technically trained and competent.
Any tampering or electrical or mechanical change, which are not previously agreed upon and authorized, cancel the Warranty of the unit.
Always observe the safety standards in force on the installation place and the provisions set by the Operative Management of the site.
Before
starting
up
the
equipment
characteristics of the power supply lines comply with the
rated values indicted on the labels positioned next to any
power
equipment
(e.g.:
fan
resistances, etc.).
In case of failure or maintenance, the power supply
equipment must be always switched off. Moreover, for any
replacement of components which should be carried out,
always apply to
our main office
Servicing
Center
of
SABIANA
original spare
parts.
The dismissed packing material (plastic, wood, polystyrene,
polyurethane, cardboard, staples, nails, etc.) must be kept
out of the reach of children for it might be dangerous for
their health and it must be disposed of or recycled correctly in
compliance with the local standards in force.
SABIANA
disclaims any responsibility for any damage to
people or thing that might come, either directly or indirectly,
from the disregard of these instructions.

Standards and certifications

TITAN
The
air
handling
the
full compliance with Standard:
2000 -
Mechanical
performance.
and classified according to Standard:
UNI
EN
13053
-
September
classifications
and
performances for units,
components and sections
with certificate issued by
Authorized Body, certifying the characteristics shown in the
table
SABIANA
is certified according to
1996
All the
SABIANA
products are provided with the
for they are manufactured in compliance with the Directives
of the European Union and relevant National Laws; therefore
each one of them comes complete with the relevant
"statement of conformity"
manuale di installazione, conduzione e manutenzione
Installation and maintenance manual

Destination of use and generalities

air treatment in the air conditioning systems
check
that
the
motors, electric heating
or an
Authorized
that
makes
use
of
units
are
manufactured
in
UNI EN 1886
- June
2007
-
UNI EN ISO 9001
since
CE
mark,
and they consist of equipment dimensioned in
TITAN
Air Handling Unit (hereunder called also UTA) and the
TUV SUD – report test number MB747
• casing strength
• casing air leakage at -400 Pa
• casing air leakage at +700 Pa
• filter bypass leakage (at + and - 400 Pa)
• thermal transmittance
• thermal bridging factor
Frequency
TUV SUD – report test number MB748
• casing strength
• casing air leakage at -400 Pa
• casing air leakage at +700 Pa
• filter bypass leakage:
+ 400 Pa = G1 - F9 / - 400 Pa = G1 - F7
• thermal transmittance
• thermal bridging factor
Frequency
23
S
PECIFICATIONS OF THE CASING
UNI-EN 1886
ACCORDING TO
G1 - F9
P
OLYURETHANE INSULATION
S
A
OUND
TTENUATION
50 mm thick panels
Hz
with polyurethane
125
dB 13,4
250
dB 16,5
500
dB 14,6
1K
dB 13,4
2K
dB 15,9
4K
dB 26,3
8K
dB 32,8
S
PECIFICATIONS OF THE CASING
UNI-EN 1886
ACCORDING TO
M
W
INERAL
OOL INSULATION
S
A
OUND
TTENUATION
50 mm thick panels
Hz
with mineral wool
125
dB 15,6
250
dB 19,8
500
dB 18,3
1K
dB 19,5
2K
dB 20,5
4K
dB 28,6
8K
dB 35,3
D1
L3
L3
T2
TB3
D1
L3
L3
T3
TB3