Electrical switchboard for gearmotors with single-phase 230V power supply or three-phase 230/400V power supply; fre- quency 50÷60 Hz. Fully designed and built by CAME Cancelli Automatici S.p.A. Box equipped with an air recirculation outlet. Guaranteed for 24 months if not tampered with.
5 Installation 5 .1 Preliminary checks 5 .1 Preliminary checks Before proceeding with installation, it is necessary to: • Check that the point of attachment of the control panel is protected from shocks, the fastening surfaces are solid, and appro- priate components (screws, plugs, etc) are used for fastening to the surface.
Page 4
5.4 Minimum thickness and wires Minimum thickness and wires Minimum thickness and wires Cable length Cable length Cable length Connections Cable type 1<10 M 10<20 M 20<30 M Power supply line, 230/400V 3F 4G 1,5mm² 4G 2,5mm² 4G 4mm² Power supply line, 230V 2F 3G 1,5mm²...
Page 5
5.5 ZT6 Electrical connections 2 C1 CX B1 B2 E4 10 11 TS 1 FC FA F 3P 4 2Mot Power supply: 230V (AC) single-phase (220-COM) Power supply: 400V (AC) three-phase (380-COM) and 230V (AC) three-phase (220-COM) Single-phase/three-phase motor 230/400V (AC) max.750 W Cycle or courtesy lamp (230V) (Cycle lamp Dip 16 OFF Dip 17 ON)-(Courtesy light Dip 16 ON Dip 17 OFF) max 60 W.
Page 6
5 5 5 .6 6 6 ZT6C electrical connections ZT6C electrical connections ZT6C electrical connections 2 C1 CX B1 B2 E4 10 11 TS 1 3P 4 FC FA F 2Mot � � � Power supply: 230V (AC) single-phase (220-Com) Power supply: 400V (AC) three-phase (380-COM) and 230V (AC) three-phase (220-COM) Single-phase/three-phase motor 230/400V (AC) max.750 W Cycle or courtesy lamp (230V) (Cycle lamp Dip 16 OFF Dip 17 ON)-(Courtesy light Dip 16 ON...
Page 7
5.7 Dip-Switches and functions SAFETY The safety features can be connected and designated for: - Re-opening Re-opening during closure (2-C1); - Re-closing Re-closing during opening (2-CX, see dip 8-9); - Partial stop Partial stop gate stops if in motion with the resulting preparation for automatic closing (2-CX, see dip 8-9); - Total stop Total stop (1-2), gate stop, excluding any automatic closing cycle;...
Page 9
5.9 Connection of two panels for control of coupled motors ���� ���� ���� ���� ���� MASTER SLAVE -Coordinate the direction of the “A” and “B” gearmotors, �� �� �� �� modifying the rotation of motor “B” (see end stop connec- ��...
Page 10
5.10 5.10 5.10 Installation of radio-controls A- INSERT AN AF CARD **. B - ENCODE TRANSMITTER/S. C - STORE CODE IN THE BASE CARD. ( A ) ( A ) AF BOARD INSERTION Frequency / board Transmitter FM 26.995 AF130 FM 30.900 AF150 AM 26.995...
Page 11
( B ) ( B ) TRANSMITTER ENCODING T434M - T314M 432S - 434MA - 432NA �� �� Set code only See instruction sheet inside the �� �� package P1 = CH1 P2 = CH2 P3 = CH3 P4 = CH4 �...
Page 12
TCH 4024 - TCH 4048 See instruction sheet inside the package T262M - T302M �� �� The first encoding operation must be carried out whilst keeping the jumpers po- sitioned for channels 1 and 2 as per fig. A; see fig. B for any subsequent settings on different channels.
Page 13
(C) CODE STORAGE - Keep the “CH1” key pressed on the base card and after the LED signal lights up, send a command using the transmitter key. The LED will flash briefly to signal that the code has been memorized (see fig. 1). - Perform the same procedure with the “CH2”...
COMMERCIAL AND OTHER CLOSING MECHANISMS (+39) 0422 4940 - fax (+39) 0422 4941 EN 12445 NDUSTRIAL COMMERCIAL AND OTHER CLOSING MECHANISMS internet: www.came.it - e-mail: info@came.it EN 12978 ..AFETY DEVICES FOR POWER OPERATED DOORS AND GATES EN 60335 - 1 AFETY IN APPARATUSES FOR HOME USE Hereby declare, under their own respons ibility, that the product/s called ...
Page 16