Siemens RDG100 Basic Documentation page 51

Room thermostats with lcd for wall mounting
Hide thumbs Also See for RDG100:
Table of Contents

Advertisement

Name
Expert level
P52
Fan operation
P53
Fan speed
P54
Fan overrun time
(only when electric heater is used)
P55
Switching point fan speed high
P55
ECM fan max. output
P56
Switching point fan speed medium
P56
ECM fan min. output
P57
Switching point fan speed low
P57
ECM: Switching point fan
P58
Fan start booster
P59
Fan min. on time
P60
Fan kick interval in Comfort mode
(time until next kick)
P61
Fan kick interval in Economy mode
(time until next kick)
P62
Clean filter reminder running time
P65
Protection heating setpoint
P66
Protection cooling setpoint
P67
Fan start delay in 2P control
P68
Extension Comfort period
P69
Temporary setpoint Comfort mode
(see also Comfort setpoint P08)
P70
Infrared receiver
P71
Reload factory settings
Name
Diagnostics and test
d01
Application type
d02
X1 status
d03
X2 status
d04
D1 status
d05
Test mode for checking
actuator direction Y1/Y2
(press left button to escape)
d06
Test mode for checking
actuator direction Y3/Y4
(press left button to escape)
d07
Software version ***)
 Parameter available
 Parameter not available
*)
If input is parameterized as analog or set to "0": "Err" is displayed when input is out of range (0...49 °C), open or shorted.
**) Thermostats with SW < 7.2 / device index < E: Factory setting = 0
***) RDG100T/H and thermostats with SW 7.2 and higher / device index E
Siemens
Building Technologies
Factory
Range
setting
1
0 = disabled
1 = enabled
2 = heating only
3 = cooling only
3-speed
1 = 1-speed
2 = 3-speed
60 s
0...360 s
100%
80..100%
ECM: 80%
ECM: fan min...100%
65%
30...75%
ECM: 30%
ECM: 0%...fan max.
10%
1...15%
ECM:10%
ECM: 0..100%
ON
ON: Enabled
OFF: Disabled
2 min.
1...6 min
OFF **)
0...89 min, OFF
OFF
0...359 min, OFF
Off (0)
OFF, 100...9900 hours
8 °C
OFF, 5...W Cool Prot;
(W Cool Prot = 40 °C max.)
OFF
OFF, W Heat Prot...40;
(W Heat Prot = 5 °C min.)
0 s
0...180 s
OFF
OFF; 15...360 min
OFF
OFF = disabled
ON = enabled
ON
OFF = disabled
ON = enabled
OFF
OFF = disabled
ON = reload start
Factory
Range
setting
Diagnostics
0 = (no application)
1 = 2-pipe
2 = 2-pipe with electric heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2 stage heating or cooling
6 = 4-pipe with electric heater
Diagnostics
0 = not activated (for DI)
1 = Activated (DI)
0...49 °C = Curr. temp. value (for AI)
Err
00
100
Diagnostics
0 = not activated (for DI)
1 = Activated (DI)
0...49 °C = Curr. temp. value (for AI)
Err
00
100
Diagnostics
0 = not activated (for DI)
1 = Activated (DI)
00
100
---
"---" = no signal at outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
---
"---" = no signal at outputs Y3 and Y4
OPE = output Y3 forced opening
CLO = output Y4 forced closing
---
Ux.xx is displayed
RDG100, RDG100T, RDG110, RDG140, RDG160
Functions
     
     x
      P52, Appl
     x
x
     x
x
     x
x
     x
      P52
      P52
      P52
      P52
     
     
    x
     
     
x
     
     
     
*)
= H/C input closed
= H/C input open
     
*)
= H/C input closed
= H/C input open
     
= H/C input closed
= H/C input open
   x
   x
     
Basic Documentation
P52
P52
x
x
x
x
 P52
P52
 P52
x
x
x
x
P52
x
x
x
x
 P52
P52
x
P52,
P46, P47
  x
x
x
x
x
P46
x
x
P47
51 / 66