Siemens RDG100 Basic Documentation page 34

Room thermostats with lcd for wall mounting
Hide thumbs Also See for RDG100:
Table of Contents

Advertisement

Modulating control: 3-position, PWM or DC 0...10 V
Heating mode (P01=0)
Y
XpH
XpH
100%
YHC2
YHC1
w
0%
w
D
Changeover (P01=2 or P01= 3)
Changeover
Y
XpH
XpH
XpC
100%
YHC2
YHC1
w
0%
w
D
Note
Setting the sequence and the control outputs
34 / 66
Siemens
Building Technologies
The diagrams below show the control sequence of modulating PI control.
TR [°C]
XpC
YHC2
YHC1
w
D
TR [°C]
The diagrams only show the PI controller's proportional part.
Refer to sections 4.5 ("Applications"), 4.7.1 ("Sequences") and 4.7.2 ("Outputs").
RDG100, RDG100T, RDG110, RDG140, RDG160
Functions
Cooling mode P01=1)
Y
XpC
100%
YHC1
w
0%
w
T[°C] Room temperature
w
Room temperature setpoint
YHC1 Control command "Stage 1"
YHC2 Control command "Stage 2"
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
X
Dead zone (P33)
dz
w
Setpoint differential (P34)
D
Basic Documentation
XpC
YHC2
TR [°C]
D
CE1P3181en
14 Dec 2011

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdg110Rdg100tRdg160Rdg100t/hRdg140