Handling Faults; Infrared Remote Control - Siemens RDG100 Basic Documentation

Room thermostats with lcd for wall mounting
Hide thumbs Also See for RDG100:
Table of Contents

Advertisement

Reloading the default timer settings
Overlapping of timer
sequences
Temperature out
of range
46 / 66
Siemens
Building Technologies
1.
Press the program mode button twice to select the "Auto timer setting"
programming mode.
2.
Press button
(OK) to enter the timer setting mode.
3.
Press the program mode button for at least 3 seconds.
"rES" will be displayed.
4.
Press button
(OK) to confirm reloading of the default timer settings
or button
(Esc) to leave without change.
The display will show "8888" during the reloading process.
When several timer sequences overlap, the resulting output is the OR combination
of the Comfort mode time of all timers.
A1 = 09:00 – 22:00
A2 = 12:00 – 20:00
Resulting output:
= 09:00 – 22:00
4.12

Handling faults

When the room temperature is outside the measuring range, i.e. above 49 °C or
below 0 °C, the limiting temperatures blink, e.g. "0 °C" or "49 °C".
In addition, the heating output is activated if the current setpoint is not set to "OFF",
the thermostat is in heating mode and the temperature is below 0 °C.
For all other cases, no output is activated.
The thermostat resumes Comfort mode after the temperature returns to within the
measuring range.
4.13

Infrared remote control

Use the IRA211 infrared remote control to operate a thermostat with built-in
infrared receiver. The following operations can be carried out remotely:
 Select Protection, Comfort or Auto Timer mode
 Adjust setpoint in Comfort mode
 Select fan mode "Automatic" or "Manual"
A buzzer in the thermostat indicates remote control command reception.
Infrared remote control can be disabled via parameter P70.
RDG100, RDG100T, RDG110, RDG140, RDG160
Functions
09:00
12:00
Basic Documentation
in
20:00 22:00
CE1P3181en
14 Dec 2011

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdg110Rdg100tRdg160Rdg100t/hRdg140