Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)
Terminal
Terminal
Block
Labels
Binary OUT
OUT n
(Jumper set
to External)
OCOM n
Binary OUT
OUT n
(Jumper Set
OCOM n
to Internal)
Configurable
OUT n
OUT
OCOM n
2,3
Sensor
Sensor
2
3
+
,
SA Bus
-
COM
SA PWR
FC Bus
+
Terminal
-
3
Block
COM
SHLD
Function and Electrical Ratings/Requirements
Binary Output, 24 VAC Triac
Connects OUT to OCOM when activated
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
The signal common for Binary OUT terminals; isolated
from all other terminal commons, including Binary Output
terminal commons
Sources 24 VAC Power (Hot)
Binary Output, 24 VAC Triac
Connects OCOM to 24 VAC Power (Com) when activated
(low side switching).
30 VAC maximum output voltage
0.5 A maximum output current
40 mA minimum load current
Analog Output, Voltage Mode
Sources 0-10 VDC
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current
Binary Output, 24 VAC Triac mode
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
Analog Output: The signal common for all analog CO
terminals; isolated from all other terminal commons,
excluding BI terminal commons
Binary Output: The signal common for binary-configured
CO terminals; isolated from all other terminal commons,
including other CO terminal commons
Provides SA Bus communication network.
RJ-12 6-position modular connector
Provides SA Bus communication network.
Provides reference for network communication bus and
15 VDC source power.
Sources 15 VDC power for devices on the SA Bus
Provides FC Bus communication network.
Provides an optional shield connection.
FEU16x0 Field Equipment Controller Installation Instructions
8
Recommended Cable Type
1
and Length
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Table 2
(See Row C in
.)
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Table 2
(See Row C in
.)
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Table 2
(See Row A in
.)
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
Table 2
(See Row C in
.)
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Same as OUT. See OUT cable
type.)
24 AWG 3-pair CAT 3 Cable
<30.5 m (100 ft)
0.6 mm (22 AWG) stranded, 4-wire
twisted, shielded cable
recommended
0.6 mm (22 AWG) stranded, 3-wire
twisted, shielded cable
recommended