3.5
Incorrect selection of type of protection
WARNING
Incorrect selection of type of protection
Danger of explosion in areas subject to explosion hazard.
This device is approved for several types of protection.
1. Decide in favor of one type of protection.
2. Connect the device in accordance with the selected type of protection.
3. In order to avoid incorrect use at a later point, make the types of protection that are not used permanently
unrecognizable on the nameplate.
3.6
Temperature transmitter for SITRANS TS500
The following head-mounted transmitters can be combined with the temperature sensors SITRANS TS500:
Transmitter
TH100
TH200
TH300
TH400
Resistance thermometers
1)
Thermocouple
2)
Note
SITRANS TS500 IEC Ex
If the contained SITRANS TH transmitter is not IEC Ex compliant, the TS500 nameplate has ATEX marking only.
3.7
Measuring inserts for SITRANS TS500
Measuring inserts for SITRANS TS500 temperature sensors are available in three variants:
● Variant 1:
DIN mounting disk for accommodating a transmitter or ceramic socket.
● Variant 2:
Fixed connection of the ends of the mineral insulated cable with a DIN ceramic socket.
● Variant 3:
Measuring insert in a spring-loaded adapter (ANSI)
SITRANS TSinsert/TS100/TS200/TS300/TS500
A5E32897098-01, 09/2013
Features
● Base device
● Output 4 ... 20 mA
● Can be configured using simple software
● P
: 12.5 mW
o
● Universal device
● Output 4 ... 20 mA
● Can be configured using simple software
● P
: 37 mW
o
● Universal
● Output 4 ... 20 mA / HART
● Diagnostic functions
● P
: 37 mW
o
● Output: PROFIBUS PA or FOUNDATION Fieldbus.
● Sensor redundancy
● Diagnostics
● P
: 12.5 mW
o
Sensor
only
1)
or
1)
2)
or
1)
2)
or
1)
2)