HORIZONTAL VENT FIGURES / TABLES (CONTINUED)
H 2
Square termination
(SV4.5HT-2) shown.
Figure 39
- Rear Vent - THREE 90 DEGREE ELBOWS
H 1
Wall Firestop/Spacer
(SV4.5HF)
See Table 12 on Page
21 as an aid in venting
component selection for
a particular range of exte-
rior wall thicknesses.
Figure 40
- Top Vent - THREE 90 DEGREE ELBOWS
Wall Firestop/Spacer
(SV4.5HF)
H 1
Ceiling
Firestop/Spacer
(SV4.5VF)
V
Firestop/Spacer
V 1
Wall Firestop/Spacer
(SV4.5HF)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
H
Maximum
+ H
+ H
1
2
feet
(meter)
5
(1.524)
10
(3.048)
15
(4.572)
20
(6.096)
H
Ceiling
(SV4.5VF)
H
Table K
H Maximum
feet
(meter)
2
(0.610)
4
(1.219)
6
(1.829)
8
(2.438)
V + H + H 1 + H 2 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H 1 + H 2 = 20 feet (6.096 meters) Max.
Example: If 20 feet total (H+H
run is needed, then 4 feet minimum of (V) vertical
vent will be required.
This table shows a 1(V) to 5(H) ratio. For every
1 foot of (V) vertical, you are allowed 5 feet of
horizontal run up to a maximum total (H+H
horizontal run of 20 feet.
See Table 12 on Page 21 as an aid in venting
component selection for a particular range of
exterior wall thicknesses.
Table L
H
Maximum
+ H
1
feet
(meter)
feet
5
(1.524)
5
(1.524)
10
(3.048)
15
(4.572)
20
(6.096)
H
+ H
= 20 feet (6.096 m) Max.
1
V
H
+ V
+
+ H
= 40 ft. (12.192 m) Max.
1
1
Example: If 20 feet total (H+H
run is needed, then 4 feet minimum of (V) vertical
V
vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1
foot of (V) vertical, you are allowed 5 feet of (H+
H
) horizontal run, up to a maximum horizontal
1
run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise
except where an elbow is the only vertical com-
ponent in the system. See Figure 35.
Square termination (SV4.5HT-2) shown.
V Minimum
feet
(meter)
1
(0.305)
2
(0.610)
3
(0.914)
4
(1.219)
+H
) horizontal vent
1
2
+H
)
1
2
V Minimum
(meter)
Elbow Only
1
(0.305)
2
(0.610)
3
(0.914)
4
(1.219)
) horizontal vent
1
23