Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guide-
line and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and
-B149.2 in Canada.
Use only approved venting components. See
Approved Vent Components on Page 2.
These fi replaces must be vented directly
to the outside.
The vent system may not service multiple
appliances, and must never be connected to a
fl ue serving a solid fuel burning appliance. The
vent pipe is tested to be run inside an enclosing
wall (such as a chase). There is no requirement
for inspection openings in the enclosing wall at
any of the joints in the vent pipe.
WARNING
Failure to reinstall and securely
tighten cover plate screws could
result in leakage of fl ue products
into the living space. Vent cover
plate and vent seal plate must
remain securely installed on
unused vent collar. Failure to do
so could result in leakage of fl ue
products into living space.
Installation of Vent Restrictor
A vent restrictor may be needed with this appliance,
install vent restrictor (provided) in the appliance top
fl ue outlet as shown in Figure 16 (SSDVT-3530
and SSDVT-4035) or rear fl ue outlet as shown in
Figure 17 (SSDVR-3530 and SSDVR-4035). It is
held in place by friction, only.
Vent Restrictor Installation
(Top Vent)
A vent restrictor may be needed when verti-
cally terminating the vent system above the
roof (when using the appliance top vent),
install vent restrictor in the top vent of the
fi replace outlet on SSDVT-3530/4035 series
models. If needed, install the restrictor orien-
tated as shown, either from inside or outside
the unit,in the inner fi replace collar.
Restrictor
Inner
Fireplace
Collar
Appliance Top
Vent Outlet
Figure 16
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
VENT RESTRICTOR INSTALLATION
(REAR VENT)
A vent restrictor may be needed when horzon-
tally terminating the vent system from the rear
of the appliance (when using the appliance rear
vent), install vent restrictor in the rear vent of
the fi replace outlet on SSDVR-3530/4035 series
models, in any installation that has a vertical
vent run in excess of three feet (0.914 meters).
If needed, install the restrictor orientated as
shown, either from inside or outside the unit, in
the inner fi replace collar
Inner Fireplace
Appliance Rear
Collar
Vent Outlet
Figure 17
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, de-
termine vent routing and identify the exterior
termination location. The following sections
describe vertical (roof) and horizontal (exterior
wall) vent applications. Refer to the section
relating to your installation. A list of approved
venting components is shown on Pages 33
through 35.
Restrictor
13