Planning; Compatibility; Defining The Place Of Installation - Siemens FDCI221 Technical Manual

Hide thumbs Also See for FDCI221:
Table of Contents

Advertisement

4 Planning

4.1 Compatibility

4.2 Defining the place of installation

Building Technologies
Fire Safety
When planning a project, proceed as follows:
1. Take into account the compatibility.
2. Define the place of installation.
3. Define the type of monitoring and configuration of the input.
4. Only for FDCIO221: Determine the output configuration
5. Fill out the configuration sheet.
Compatible with control panels that support the FDnet/C-NET detector line.
Detector line
FC20xx
FDnet
X
C-NET
With suitable line card
1
X = compatible
– = not compatible
You will find detailed information in the 'List of compatibility'.
Installation specification for controlling fire protection installations
For the purpose of controlling fire protection installations in accordance with
EN 54-2, the input/output module FDCIO221 must be integrated into the fire control
housing.
Installation specification for controlling the VdS extinguishing
interface
If the input/output module FDCIO221 is used to control the VdS extinguishing
interface, it must be installed in the control panel housing. Details are described in
the control panel documentation.
Defining the place of installation
Install the module as close as possible to the fire control. This simplifies the
cabling.
Use the housing FDCH221 for the following installation situations:
Outside a switch cabinet
Outside a control panel
In a wet or dirty environment
FC72x
SIGMASYS
X
1
X
Planning
4
Compatibility
AlgoRex
FC360
X
1
X
35 | 50
A6V10211122_m_en_--
2018-09-18