Planning
4
Compatibility
4 Planning
4.1 Compatibility
50 | 72
Building Technologies
Fire Safety
When planning a project, proceed as follows:
1. Define the mounting site and configuration of the lines
2. Plan the various line types:
–
Collective detector line
–
Collective detector line for areas at risk of explosion (zone 1 and zone 2)
–
Conventional detector line
–
Control lines
–
Contact inputs
The input/output module FDCIO223 is compatible with the following fire detection
systems:
Sinteso FS20
Cerberus PRO FS720
SIGMASYS
AlgoRex
Detector line
FC20xx
FDnet
X
C-NET
–
X = compatible
– = not compatible
You will find detailed information in the 'List of compatibility'.
Limitations
Maximum of 32 devices per collective detector line if each device has a KMK =
1
If devices have a KMK >1, the maximum number of devices per collective
detector line decreases accordingly.
See also
Applicable documents [
Control panel
FC72x
SIGMASYS
-
X
X
–
8]
AlgoRex
X
–
009122_h_en_--
2016-05-04