4.4 Defining the output configuration

4.5 Filling out the configuration sheet

Building Technologies
Fire Safety
When configuring the outputs, please proceed as follows:
1. Define the type of output:
Bistable, switched voltage, normal operation
(option of monitoring output lines)
Bistable, switched voltage, inverted operation (output lines not monitored)
Bistable, potential-free contact (output not monitored)
2. Mount the jumper onto 'J2' or 'J1' depending on your selection.
3. Determine in which position the contact is active. The contact may be active
when it is:
Closed (NO)
Open (NC)
4. Define how long the output shall remain active after activation. The output can
be:
Permanently active.
Active only for a certain period of time. How long the output remains active
can also be configured (pulse duration).
5. Determine the behavior of the output in case of error (e.g., open line to the
control panel).
The following configurations are possible for the behavior in case of a failure:
Output remains the same as before the error
Output is activated in case of an error
Output is deactivated in case of an error
Output remains the same as before the error, but responds to the
'Degraded mode horn' signal like other sounders on the detector line
Pulse duration
The following settings are possible for pulse duration:
1 s
10 s
See also
2 Output (for input/output module only) [
Proceed as follows when filling out the configuration sheet:
1. Copy out the configuration sheet. You will find it in the appendix.
2. Fill out the configuration sheet.
3. Hand over copies of the completed configuration sheet to the installer and the
service technician.
See also
2 Configuration sheet [
Defining the output configuration
2 s
3 s
15 s
20 s
46]
Planning
4
5 s
25]
37 | 50