Model FDCIO422
Addressable Input/Output module
Installation Instructions
INTRODUCTION
The FDCIO422 is used for the connection of up
to 2 independent Class A or 4 independent
Class B dry N/O configurable contacts. Input
lines can be supervised for open, short and
ground fault conditions (depending on EOL
termination resistor and class configuration).
Inputs can be independently configured via the
fire control panel for alarm, trouble, status or
supervisory zones.
The FDCIO422 has 4 programmable outputs
with 4 potential-free latching type form A relay
contacts for fire control installations.
Status indication per LED for each input and
output plus 1 LED for general status of the
device. Power supply via FDnet (supervised
power limited).
· Including 4 EOL devices (470 Ω)
· 3 separators to separate the power limited
wiring from the non-power limited.
Separators are delivered in 3 different sizes
11
for standard 4
/
16
extension ring and 5-inch box (RANDL).
Figure 2 Removing the cage and the terminal strips from the carrier
A6V10324662_g_en_US
2016-01-20
11
-inch box, 4
/
-inch
16
Download link Desigo:
https://www.buildingtechnologies.siemens.com/extranet/ba-sp/
Download link Cerberus PRO:
http://iknow.us009.siemens.net/infolink
Figure 1 FDCIO422 cage and carrier
CAUTION
This device is not intended for
applications in explosive environments.
Class A is equivalent to DCLA (Canada)
Class B is equivalent to DCLB (Canada)
For complete configuration and
commissioning of the FDCIO422 also refer
to the user documentation of your panel,
especially for the software tool used for
configuration.
SIEMENS Industry, Inc.
S54322-F4-A1
CAUTION
Electric shock!
High voltages may
occur on the terminals.
Always use a faceplate
and the separator(s).
Building Technologies Division