Section 6 - Samlexpower Evolution Series Owner's Manual

Inverter / charger pure sine wave
Hide thumbs Also See for Evolution Series:
Table of Contents

Advertisement

SECTION 5 |
5.8.2.2.1 During the 2nd "Absorption Stage", the batteries will be charged at constant voltage (CV) = the
programmed value of parameter "ABSORP VOLTAGE" [Default value of parameter "ABSORP VOLTAGE" is 14.4V for
EVO-1212F/1212F-HW and 28.8V for EVO-1224F/1224F-HW. See programming range at Table 6.2, Section 6 and
programming procedure at Section 4.4.2.2 in the EVO-RC-PLUS Remote Control Manual]. The Absorption Stage is
displayed as "E-Absorption Stage" in the 2
refer to codes / abbreviations detailed at Table 3.2 under Section 3.6.4.3 of EVO-RC-PLUS Remote Control Manual].
The charger remains in this stage for computed Time T1' [Refer to Section 5.8.2.1.2(a)] and then transitions to Stage
3 – Equalization Stage described at Section 5.8.2.3 below
5.8.2.3 Stage 3 –Adaptive Equalization Stage:
Refer Section 1.4.3.4 for general information on Equalization Stage and to Fig 5.2 for voltage and current curves during
this stage
In this stage, charging takes place at constant voltage at value = the programmed value of parameter "EQUALIZE
VOLTAGE" [Default value is 14.40V for EVO-1212F/1212F-HW and 28.8V for EVO-1224F/1224F-HW. Please see
programming range at Table 6.2 and programming procedure at Section 4.4.2.3 in EVO-RC-PLUS Remote Control
Manual]. It remains in this stage for computed time "T2" [Refer to Section 5.8.2.1.2(b)] and then transitions to Stage 4
described at Section 5.8.2.4 below
5.8.2.4 Stage 4 – Last Stage of 4-Stage Charging Profile for Equalization:
Stage 4 of the 4-Stage Charging Profile for Equalization will be the same as the last stage of the charging profile that
was active when the 4-Stage Charging Profile for Equalization was switched on. See details at Table 5.2.1 below:
Table 5.2.1 Stage 4 of 4-Stage Adaptive Charging Profile for Equalization
Charging Profile that was active
when Equalization was started
(1)
0=3 Stage Adaptive
1=3 Stage Type 1
2= 3 Stage Type 2
3= 2 Stage Type 1
4= 2 Stage Type 2
5= 2 Stage Type 3
NOTE 1:
This portion of display is shown in the 2
Menu Map for Charging Mode Screens at Fig 3.3(a) under Section 3.6.4.1 of EVO-RC-PLUS Remote Control Manual].
106 | SAMLEX AMERICA INC.
Battery Charging in Evolution™ Series
line of Charging Mode Screens of EVO-RC-PLUS Remote Control. [Please
nd
Last Stage of Charging Profile at Column
(1) from where Equalization was started
FLOAT: Charge at constant voltage =
"FLOATING VOLTAGE"
• Exit to BULK STAGE when:
Voltage drops to "RESET TO BULK", or
o
After 10 days in Float Stage
o
OFF
Absorption Stage
Off
line of Charging Mode display screens [Refer to scrollable screens 1 to 5 of
nd
(2)
EVO-RC display at 1st line, right
corner (See Note 1)
(3)
0 - Float Stage
1 - Float Stage
2 - Float Stage
3 - Charger Off
4 - Absorption Stage
5 - Charger Off