ESIE-0303
Model
Casing
Material
Colour
Sound power level
Safety devices
(1)
: The table below contains the minimum water volume settings.
Setting
The minimum water volume for standard thermostat difference setting
For reduced setting multiply this water volume by
Minimum allowable setting
(2)
: The sound power level is an absolute value that does not depend on the surroundings or the
Nominal conditions
The nominal conditions are as follows:
■
■
■
Operation range
The nominal operation range covers a leaving evaporator water temperature from 5°C (-5°C/ -10°C
with ZH/ ZL option) to 20°C and a leaving condenser water temperature from 20°C to 55°C.
Part 1 – System Outline
EUW5KZW1
(2)
■
Low-pressure switch
■
High-pressure switch
■
Evaporating temperature protection
■
Discharge temperature protection
■
Outlet water temperature protection
■
Compressor motor overcurrent relay
■
Anti-recycling and guard timer
■
Digital display controller with electronic temperature control
■
Reverse phase protector
■
Internal fuses.
distance (ISO 9614). It cannot be measured in the field
Entering/leaving evaporator water temperature 12/7°C, ambient air temperature 35°C,
Entering/leaving condenser water temperature 30/35°, ambient temperature 7°C DB/6°C WB
Power input is total input: Compressor + control circuit + pumps.
EUW8KZW1
Polyester coated / galvanised steel plate
Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
64 dB
General Outline
EUW10KZW1
EUW5-10KZW1
3 K
3/new setting
0.1 K
1
3
4
5
1–5