ESIE-0303
Fans
The table below contains the settings of the fans.
Code
f1
Anti-freeze and
The table below contains the settings of the anti-freeze and the supporting heaters.
supporting heaters
Code
a1
a2
a3
a7
Alarm
The table below contains the settings of the alarm.
Code
p1
p2
p3
p4
p5
p8
p9
pa
pb
pv
Part 3 – Troubleshooting
Parameter
Function
Factory
Are there any fans?
Parameter
Function
Factory
Anti-freeze alarm set
point
Factory
Anti-freeze alarm hysteresis
Factory
Bypass time for anti-freeze alarm
Factory
Limit anti-freeze alarm set
Parameter
Function
Factory
Flow-start timer
Factory
Flow-stop timer
Factory
LP bypass timer
User
Buzzer ON time
Factory
Reset of alarms
Factory
Selection of digital input ID1
Factory
Selection of digital input ID2
Factory
LP alarm when the compr. is OFF
Factory
High temperature alarm set
Factory
High temperature alarm delayed at
start-up
EUW(L)5-24KZW1
0
EUW5-24KZW1
EUWL5-24KZW1
Standard
4°C
ZL option
-11.5°C
ZH option
-6.5°C
3.5°C
0 s
-15°C
EUW5-24KZW1
EUWL5-24KZW1
20 s
5 s
60 s
1 min.
0
1
8
0
90°C
30 min.
Troubleshooting
1
Read/
write
r/w
Read/
3 3
write
r/w
4
5
Read/
write
r/w
3–27