ESIE-0303
Malfunction
High-pressure
switch
Flow switch or
pump contact
Discharge ther-
mal protector
Reverse phase
protection
An overview of the malfunction indications and safeties is given in "Malfunction Indications and
Safeties Overview" on page 3–7.
Part 3 – Troubleshooting
Possible causes
Defective condenser fan
operation in cooling
Dirty or blocked condenser
Operation out of range
Water flow too low in heating
Water temperature too high in
heating
Damaged flow switch
Incorrect pump operation
Incorrect field wiring
Defective control devices
(pump relay)
Refrigerant shortage
Operation out of range
Incorrect phase direction
One phase missing
Troubleshooting
Items to be checked
Operation condition
outdoor air temp. < 43°C
State of the condenser (clean)
Pump operation
Water flow (blocked valves)
Flow switch operation
Operation condition
leaving condenser water < 55°C
Flow switch
Pump operation
Field wiring
Control devices
Refrigerant leak
Operation condition
Swap two phases
Connect the loose phase
1
3 3
4
5
3–21