Components
The table below describes the components.
refrigeration side
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
Part 1 – System Outline
Component
Function / remark
Compressor
A hermetically sealed scroll compressor.
Water-heat exchanger
The water-heat exchanger is of the brazed plate-heat exchanger
(evaporator)
type.
Expansion valve
The thermostatic expansion valve is set up to control the
superheat between 5°C and 7°C.
Low-pressure switch
This switch acts as a circuit safety.
High-pressure switch
This switch acts as a circuit safety.
Strainer
This strainer prevents dirt particles from entering the expansion
valve.
Water in- and outlet
The water in- and outlet connections are made of galvanized
connections
steel pipe (British Standard Pipe - BSP). The pipes are not
insulated.
If copper field piping is used for the water circuit, then precau-
tion should be taken to prevent electrolytic corrosion.
Low-pressure
The low-pressure service port is used to connect a
service port
low-pressure gauge.
sight glass with
moisture indicator
Water temperature
The water temperature sensors are used to control the
sensor
thermostat function at the heat exchanger inlet.
Freeze-up sensor
This protection device shuts down the circuit when the tempera-
ture of the chilled water becomes too low in order to prevent the
water from freezing during operation.
Accumulator
The accumulator is used to prevent the liquid refrigerant from
entering the compressor.
Liquid solenoid valve
The liquid solenoid valve prevents that the evaporator from filling
with liquid if the unit is switched off.
Standard setting: OFF = 1.2 bar ± 0.2
Standard setting: ON = 2 bar ± 0.3
ZL/ZH setting: OFF = 0.5 bar ± 0.2
ZL/ZH setting: ON = 1.5 bar ± 0.3
Standard setting: OFF = 30.9 bar +0/-1
Standard setting: ON = 21.6 bar ± 0.1
Piping Layout
1
3
4
5
1–41