Test Run and Operation Data
2.2
Currents and Used Fuses
1
Currents
3
4
5
4–16
The table below contains the currents and used fuses.
Unit
Nominal current
EUW5KZW1
6.6 A
EUW8KZW1
10.4 A
EUW10KZW1
13.1 A
EUW12KZW1
15.0 A
EUW16KZW1
20.8 A
EUW20KZW1
26.2 A
EUW24KZW1
30.0 A
Recommended fuses according to IEC standard 269-2: gL/gG (aM also admitted)
(F1U, F2U, F3U = gL/gG)
Maximum current
Fuses
13 A
3 x 16 gL/gG
19 A
3 x 20 gL/gG
23 A
3 x 25 gL/gG
23 A
3 x 25 gL/gG
33 A
3 x 35 gL/gG
41 A
3 x 40 gL/gG
45 A
3 x 50 gL/gG