Water quality
The table below contains the required water quality specifications.
Items to be checked
pH
at 25°C
Electrical conductivity
mS/m
(at 25°C)
Chloride ion
mg Cl
Sulphate ion
mg SO
M-alkalinity (pH 4.8)
mg CaCO
Total hardness
mg CaCO
Calcium hardness
mg CaCO
Silica ion
mg SiO
Items to be referred to
Iron
mg Fe/l
Copper
mg Cu/l
Sulphide ion
mg S
Ammonium ion
mg NH
Remaining chloride
mg Cl/l
Free carbide
mg CO
Stability index
Part 4 – Commissioning and Test Run
Evaporator water
Circulating
Supply water
water (< 20°C)
6.8~8.0
6.8~8.0
< 40
< 30
-
< 50
< 50
/l
< 50
< 50
2-
/l
4
/l
< 50
< 50
3
/l
< 70
< 70
3
/l
< 50
< 50
3
/l
< 30
< 30
2
< 1.0
< 0.3
< 1.0
< 0.1
2-
Not detectable
Not detectable
/l
+
< 1.0
< 0.1
/l
4
< 0.3
< 0.3
/l
< 4.0
< 4.0
2
Heated water (low temperature)
Circulating water
Supply water
(20°C-60°C)
7.0~8.0
7.0~8.0
< 30
< 30
< 50
< 50
< 50
< 50
< 50
< 50
< 70
< 70
< 50
< 50
< 30
< 30
< 1.0
< 0.3
< 1.0
< 0.1
Not detectable
Not detectable
< 0.3
< 0.1
< 0.25
< 0.3
< 0.4
< 4.0
Pre-Test Run Checks
Tendency if out of
criteria
Corrosion + scale
Corrosion + scale
Corrosion
Corrosion
Scale
Scale
Scale
4
Scale
Corrosion + scale
Corrosion
Corrosion
Corrosion
Corrosion
Corrosion
Corrosion + scale
4–7