13.0 Network Options

Network options define the way in which the panel is configured to operate on a networked system. These
options, such as the panel address, should be checked when a system is first installed, but will rarely need
altering after this time.
A summary of the network options for various network configurations is given below. Refer to the
D8024/D10024A Networking Guide (P/N 34377) for further detailed information.
Press 3 to select the 'Network' option from Page 3 of the commission menus.
To change a setting, press either CHANGE or NO and then enter the desired setting. Step on using the YES
key.
13.1

Panel Networks

13.1.1

Network - Panel Network Address

The Network Address will have been set when the panel leaves the factory. It may need to be changed,
however, when the panel is installed in a network system. If the panel is not required on a network, then this
address should be set to 1.
Each panel should be given a
unique panel address
number.
13.1.2

Standard Network Settings for shared zones

The following tables give typical settings for shared zone mini-network system.
Network Option
Panel network-address
number
Quantity of slave processors
Use modem
Share zones
Peer-to-Peer
*Port B Protocol
System events
© 2002 Radionics
Option setting
1..20
0
[TRUE]/[FALSE]
[TRUE ]
[TRUE]
0
[GLOBAL]/[LOCAL ]

Table 14: Slave Panel Network Settings

D8024/D10024A Operation and Installation Guide
Page 47
Comments
Enter slave panel address, i.e. 3.
Number of slaves connected to port C.
MUST be set to FALSE
Zones are shared between panels
Pass TROUBLE SILENCE, ALARM SILENCE and
RESET key presses back to master.
Use default of 0 unless special application interface
Global -
passes system events over network accepts
other network events.
Local -
does not pass events over the network.
Ignores other network events.
NOTE: The zonal fire status is passed over a
shared-zone network regardless of events being
global or local.
D8024/D10024A