Commissioning Delayed Mode

Press 1 to select Delayed mode from the 'Day Modes Menu.
The display will prompt
whether the mode is to be
used.
Press No to inhibit the mode and return to the 'Day Mode' menu.
Press Yes to enable the mode.
The display will then prompt
the start and end times for the
day period.
Press Yes to accept and step on.
Press No to change and then
enter the required start time
using the number buttons.
Press Yes to accept and step on. Press No to change and then enter the required end time using the
number buttons.
A two stage timer is built into the day mode.
After entry of the start / end
times, the display prompts the
stage timers as follows:
Press Yes to accept and step on.
Press No to change and then
enter the required end time
using the number buttons.
Immediately a fire is detected. If this Stage 1 alarm is not acknowledged at the panel by pressing the
"TROUBLE SILENCE" button within the 15 seconds a full alarm will be generated.
Pressing the "TROUBLE SILENCE" button within this period will cause stage 2 to be entered.
The stage 2 timer will start counting down as soon the panel detects an alarm signal (i.e. starts at the same
time as stage 1). Setting the stage 2 time for a longer period than stage 1 provides the user with the
opportunity to investigate the cause of the alarm and take appropriate action. If the panel is not reset by the
time stage 2 has expired, a full fire alarm will be raised.
Finally, the display prompts
the zones that are to be used
in delayed mode.
The above example shows that zones 1 to 12 inclusive will not use the day mode times and hence, a fire
alarm will be generated immediately any sensor in these zones detects a high sensor reading.
To change the zones, use the '<' or '>' to select the appropriate field. Use the number keys to change the
zone numbers. Use the Change key to toggle between [TRUE] and [FALSE].
The user can choose to enable and disable the delayed day mode at level 2. This is as described in
the user manual.
Per NFPA 72 1999, paragraph 1-5.4.11 the maximum times for the Stage 1 and Stage 2
timers are as follows:
Stage 1 = 15 seconds
Stage 2 = 180 seconds
50616B
D8024/D10024A Operation and Installation Guide
Page 42