12 - OPERATION OF 30WG UNITS WITH SPECIFIC HEATING CONTROL (OPTION 153)

12.1 - Operating principle

Units have been designed to optimise the operation of heating installations that require hot-water production for a traditional heating
system and domestic hot-water production.
The TouchPilot Junior control system of the units includes algorithms that permit constant automatic optimisation of:
- control of a directional on/off three-way valve based on the heating or domestic hot water requirements
- control of the electric heating stages allowing relief of the heating loop
- hot-water setpoint reset (heating application) based on the air temperature
- priority control between heating application and domestic hot-water application.
NOTE: The installer is responsible for ensuring that the installation complies with the applicable legislation in terms of
electrical and thermal safety.

12.2 - Auxiliary electronic board (AUX1) - analogue and digital inputs and outputs

- Connector J2: Digital outputs CH 1 to 4 for electricals heaters 1 to 4.
- Connector J3: Digital output CH 6 to control a directional on/off three-way valve
- Connector J6: Analogue input CH 11 for outside air temperature sensors
- Connector J6: Analogue input CH 12 for information on domestic hot water demand
- Connector J7: Analogue input CH 13 for information on domestic hot water demand
- Connector J8: Analogue input CH 14 for information on summer operation only (domestic hot water only)
To apply the different configurations required, refer to the instructions in the TouchPilot Junior Control IOM.
54
J2
J3
CH
CH
CH
CH
CH
CH
CH
CH
--
--
--
--
--
--
--
1
2
3
4
5
6
7
8
STATUS
SIO
CH14
T
P
V
T
P
V
CH13
J4
J5
J6
--
CH
CH
--
--
CH
--
CH
--
9
10
11
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquasnap 30wg seriesAquasnap 30wga series

Table of Contents