5 - APPLICATION DATA

5.1 - Operating limits 61WG/30WG/WGA

30WG
Evaporator
Entering water temperature at start-up
Leaving water temperature during operation °C
Entering/leaving water temperature difference K
Condenser
Entering water temperature at start-up
Leaving water temperature during operation °C
Entering/leaving water temperature difference K
(1) For entering water temperatures below 7.5 °C at start-up, contact manufacturer.
(2) If the leaving water temperature is below 5 °C, a frost protection solution must
be used. Please refer to option 6 for evaporator leaving water low-temperature
applications (< 5 °C).
(3) For applications with a condenser entering temperature below 15 °C the use of
a three-way valve is recommended. This three-way valve can be controlled by
the 0-10 V analogue output of the TouchPilot Junior control.
(4)  For a water flow rate that corresponds to a maximum water-side temperature 
difference of 5 K.
30WG + option 6
Evaporator
Entering water temperature at start-up
Leaving water temperature during operation °C
Entering/leaving water temperature difference K
Condenser
Entering water temperature at start-up
Leaving water temperature during operation °C
Entering/leaving water temperature difference K
Note: Do not exceed the maximum operating temperature.
(1) A frost protection solution must be used.
(2) For applications with a condenser entering temperature below 15 °C the use of
a three-way valve is recommended. This three-way valve can be controlled by
the 0-10 V analogue output of the TouchPilot Junior control.
(3)  For a water flow rate that corresponds to a maximum water-side temperature 
difference of 5 K.
30WG + drycooler
Evaporator
Entering water temperature at start-up
Leaving water temperature during operation °C
Entering/leaving water temperature difference K
Condenser without hydraulic module
Entering air temperature at start-up + during
operation
Condenser with option 270V (kit with
variable-speed pump)
Entering air temperature at start-up+ during
operation
(1) For entering water temperatures below 7.5 °C at start-up, contact Carrier.
(2) If the leaving water temperature is below 5 °C, a frost protection solution must
be used. Please refer to option 6 for evaporator leaving water low-temperature
applications (< 5 °C).
(3) The minimum entering air temperature is based on the drycooler selection.
(4) The maximum entering air temperature is based on the drycooler selection.
(5) For applications with a low condenser entering air temperature the use of a
three-way valve is recommended. This thre-way valve can be controlled by the
0-10 V analogue output of the TouchPilot Junior control.
38
Minimum Maximum
61WG
Evaporator
Entering water temperature at start-up
°C
7.5
(1)
27
Leaving water temperature during operation °C
5
20
(2)
Entering/leaving water temperature difference K
2.5
7
Condenser
Entering water temperature at start-up
°C
15
55
(3)
(4)
Leaving water temperature during operation °C
20
60
Entering/leaving water temperature difference K
2.5
18
(1) For entering water temperatures below 7.5 °C at start-up, contact Carrier.
(2) If the leaving water temperature is below 5 °C, a frost protection solution must
(3) For applications with a condenser entering temperature below 15 °C the use of
(4)  For a water flow rate that corresponds to a maximum water-side temperature 
61WG + option 272 (geothermal application)
Minimum Maximum
Evaporator
Entering water temperature at start-up
°C
-9.5
27
(1)
Leaving water temperature during operation °C
-12
20
(1)
Entering/leaving water temperature difference K
2.5
5
Condenser
Entering water temperature at start-up
55
°C
15
(2)
(3)
Leaving water temperature during operation °C
20
60
Entering/leaving water temperature difference K
2.5
18
(1) A frost protection solution must be used.
(2) For applications with a condenser entering temperature below 15 °C the use of
(3)  For a water flow rate that corresponds to a maximum water-side temperature 
30WGA
Evaporator
Minimum Maximum
Entering water temperature at start-up
Leaving water temperature during
°C
7.5
27
(1)
operation
5
20
(2)
Entering/leaving water temperature
2.5
7
difference
Air entering temperature (at start-up and
during operation)
°C
10-15
40-45
(3)
(4)
Air entering temperature (fixed-speed fan) °C
Air entering temperature (variable-speed
fan)
°C
-10
(5)
40-45
(4)
(1) For entering water temperatures below 7.5 °C at start-up, contact Carrier.
(2) 30WGA unit can operate down to 0 °C if the option 5B brine down to 0°c is used.
(3) The minimum temperature range is based on the condenser selected.
(4) The maximum temperature range is based on the condenser selected.
be used. Please refer to option 272 for evaporator leaving water low-temperature
applications (< 5 °C).
a three-way valve is recommended. This three-way valve can be controlled by
the 0-10 V analogue output of the TouchPilot Junior control.
difference of 5 K.
a three-way valve is recommended. This three-way valve can be controlled by
the 0-10 V analogue output of the Touch Pilot Junior control.
difference of 5 K.
(2)
30WGA + Opt 5B
Evaporator
Entering water temperature at start-up
Leaving water temperature during operation °C
Entering/leaving water temperature
difference
Air entering temperature (at start-up and
during operation)
(3)
Air entering temperature (fixed-speed fan) °C
Air entering temperature (variable-speed
fan)
If the leaving water temperature is below 5 °C, a frost protection solution must
be used.
Minimum Maximum
°C
7.5
(1)
27
5
20
(2)
2.5
7
°C
15
60
(3)
(4)
20
65
2.5
18
Minimum Maximum
°C
-2.5
(1)
25
-5
(1)
20
2.5
5
°C
15
60
(2)
(3)
20
65
2.5
18
Minimum
Maximum
°C
7.5
27
(1)
°C
5
(2)
20
K
2,5
7
0
35 to 48
(2)
(4)
°C -10 to -20
35 to 48
(3)
(4)
Minimum Maximum
°C
7.5
(1)
27
0
(2)
20
K
2,5
7
0
35 to 48
(3)
(4)
-10 to
°C
35 to 48
(4)
-20
(3)