30Wg/61Wg Unit Operation With A Drycooler (Option 154); Operating Principle; Communication To Control The Drycooler; Configuration Of The Number Of Fan Stages And The Automatic Changeover Of The Fan Stages - Carrier AquaSnap 61WG Series Installation, Operation And Maintenance Instructions

Water-cooled/condenserless liquid chillers/water-sourced heat pumps with or without integrated hydraulic module
Hide thumbs Also See for AquaSnap 61WG Series:
Table of Contents

Advertisement

14 - 30WG/61WG UNIT OPERATION WITH A DRYCOOLER (OPTION 154)

14.1 - Operating principle

The units have been designed to optimise the operation of
systems, using drycoolers as heat rejection system.
With a variable-speed condenser water pump integrated into the
unit the complexity of traditional systems, using a three-way valve
has been reduced.
The installation of an operational system is limited on the
condensing water loop side to connect the drycooler entering and
leaving water piping to the unit.
The TouchPilot Junior control of the unit includes algorithms to
permit constant automatic optimisation of:
- drycooler fan stage operation
- water flow rate variation in the loop between the condenser 
and the drycooler.
Parallel control of the fan stages (up to 8 stages maximum) and
of the variable water flow rate of the loop permit year-round system 
operation down to -10 °C outside temperature without any
additional control.

14.2 - Communication to control the drycooler

The electronic board specifically integrated in the control box of 
the drycooler, by an option selection on the manufacturer drycooler,
and a communication LEN bus connected to the microprocessor
board of the unit is used for the overall system control.
Pay attention that Dry cooler and Chiller have to be both equipped
with the option Drycooler Management (Opt154)
The option is supplied in the manufacturer's drycooler control box.
Connect the unit to board AUX1 in the drycooler, using a
communication cable. the communication cable should be connect
to the plug with 3 points Wago type (5 mm spacing or equivalent).
the communication cable should be a shielded type.
TouchPilot Junior optimises system operation to obtain the best
efficiency with variation of the water flow rate and the number of 
fans required for any thermal load and outside temperature
conditions.
The electronic board (AUX1) integrated in the control box of the
drycooler has analogue inputs for outside air temperature and
drycooler leaving water temperature sensors, as well as eight digital
outputs permitting control of up to eight fan stages.
14.3 - Configuration of the number of fan
stages and the automatic changeover of the fan
stages
Please refer to the instructions in the TouchPilot Junior IOM for the
configuration  of  the  number  of  fan  stages  to  be  controlled.  It  is 
enough to enter the number of fan stages of the drycooler in the
TouchPilot Junior service menu. The number of digital outputs
controlling the fans are activated by the control.
TouchPilot Junior controls the automatic switching of all fan stages,
based on operating time and number of start-ups of the different
stages. This function prevents fan motors from only running a little
or not at all and the shafts seizing up, especially during periods
with a low cooling demand, when the outside temperature is low.
Switching  is  often  specified  by  the  drycooler  manufacturers  to 
ensure a long operating life of fan motors that are only used a little
or not at all in these particular operating conditions.
56

14.4 - Fan stage assignment

The minimum configuration of the number of fan stages is 2 for 
correct operation.
Depending on the drycooler capacity the number of fans can be
between 2 and 8. They can be controlled by one fan or by linked
pairs, if necessary.
A drycooler with 4 or 6 fans installed in series for example along
the  length  of  the  unit  will  result  in  a  configuration  of  4  or  6  fan 
stages.
Reciprocally a drycooler with 8 or 12 fans arranged in pairs along
the length of the unit will also result in a configuration of 4 or 6 fan 
stages.
Configuration with 4 and 6 stages (min. 2 - max. 8)
A
1
Fans linked in pairs - 4 and 6-stage configuration
(min. 2 - max. 8)
1
A
1
Legend
A
Entering and leaving water manifold side
1 to 6
Fans
14.5 - Units without evaporator and condenser
pump, three-way valve configuration for low
outside temperature application
Units can be supplied from the factory without evapo-rator and
condenser pump. If year-round low-temperature operation is
planned, the unit will be installed with a three-way valve that is
not supplied with the unit.
In this case TouchPilot Junior should be configured for three-way 
valve system control from an analogue 0-10 volt output on the
master board. An adequate condensing temperature will be
maintained with constant condenser flow rate. This configuration 
permits year-round system operation down to -20 °C outside
temperature.
Control and changeover of the fan stages, described in chapter
"Configuration of the number of fan stages and automatic
changeover of the fan stages" is identical in this case.

14.6 - Drycooler installation on units

For the drycooler installation follow professional guidelines.
- Water pipe sizing
- Maximum piping and shut-off valve pressure drops based on
the available pressure of the unit pumps
- Maximum drycooler elevation in relation to the unit (relief
valve at 4 bar on the unit water circuit).
- Fan stage control (see "Fan stage control").
- Good positioning of the outside air temperature and drycooler
leaving water temperature sensors.
2
3
4
5
2
3
4
5
2
3
4
5
6
6
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquasnap 30wg seriesAquasnap 30wga series

Table of Contents