ds6: absorption time 8 or 4 hours
(not relevant for L2, L3)
ds5: adaptive charging characteristic on = active
(not relevant for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency
(not relevant for L2, L3)
(note: the wide input frequency range (45-65z) is 'on' by default)
Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by
computer, all DIP switches of a new product are always in 'off' position).
DS-8 Ch. voltage
DS-7 Ch. voltage
DS-6 Absorpt. time
DS-5 Adaptive ch.
DS-4 Dyn. Curr. limit
DS-3 UPS function:
DS-2 Voltage
DS-1 Frequency
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 120V
1 Frequency: 60Hz
To store the settings after the required values have been set: press the
'Down' button for 2 seconds (lower button to the right of the DIP switches).
The temperature and low-battery LEDs will flash to indicate acceptance
of the settings.
You can then leave the DIP switches in the selected positions, so that the
'other settings' can always be recovered.
42
off
DS-8
on
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Absorption time: 8 h
5 Adaptive charging:
on
4 Dyn. current limit: off
3 UPS function: off
2 Voltage: 120V
1 Frequency: 60Hz
on = 8 hours off = 4 hours
on = active
on = active
on = 120V
on = 50Hz
off
DS-8
off
DS-7
on
DS-6
on
DS-5
off
DS-4
off
DS-3
on
DS-2
off
DS-1
Step 2
Example 3:
8, 7 AGM 14,7V
6 Absorption time: 8 h
5 Adaptive charging: on
4 Dyn. current limit: on
3 UPS function: off
2 Voltage: 115V
1 Frequency: 60Hz
off = inactive
(fixed absorption time)
off = inactive
off = inactive
off = 115V
off = 60Hz
on
DS-8
off
DS-7
on
DS-6
on
DS-5
on
DS-4
off
DS-3
off
DS-2
off
DS-1
Step 2
Example 4:
8, 7 Tubular-plate 15V
6 Absorption time: 4 h
5 Fixed absorption time
4 Dyn. current limit: off
3 UPS function: on
2 Voltage: 115V
1 Frequency: 50Hz
on
on
off
off
off
on
off
on