Parallel operation (see appendix C)
Step 1: Setting ds2 and ds1 for parallel operation of two or three units
Master
DS-8 AC-in-1
Set
DS-7 AC-in-1
Set
DS-6 AC-in-1
Set
DS-5 AC-in-2
Set
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Master
DS-1 Master
The current settings (AC current limitation and charging current) are
multiplied by the number of devices. However, the AC current limitation
setting when using a remote panel will always correspond to the value
indicated on the panel and should not be multiplied by the number of devices.
Example: 15kVA parallel system
-
If an AC-in-1 current limitation of 35A is set on the master and the
system consists of three devices, then the effective system current
limitation for AC-in-1 is equal to 3 x 35 = 105A (setting for generator
power 105 x 120 = 12.6kVA).
-
If a 30A panel is connected to the master, the system current
limitation for AC-in-2 is adjustable to a maximum of 30A, regardless
of the number of devices.
-
If the charging current on the master is set to 100% (120A for a
Quattro 24/5000/120) and the system consists of three devices,
then the effective system charging current is equal to 3 x 120 =
360A.
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
off
DS-2 Slave 1
on
DS-1 Slave 1
Slave 1
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
off
DS-2 Slave 2
off
DS-1 Slave 2
Slave 2 (optional)
off
on
37