Procedure: set the DIP switches to the required value:
ds8 ds7 ds6
off
off
off
off
off
on
off
on
on
off
on
off
on
on
on
on
Remark:
Manufacturer-specified continuous power ratings for small
generators are sometimes inclined to be rather optimistic. In
that case, the current limit should be set to a much lower
value than would otherwise be required on the basis of
manufacturer-specified data.
AC-in-2 can be set in two steps using DIP switch ds5 (default setting: 30A).
Procedure: set ds5 to the required value:
ds5
off = 30A
on = 50A
5.5.1.3 Charging current limitation (default setting 75%)
For maximum battery life, a charging current of 10% to 20% of the capacity in
Ah should be applied.
Example: optimal charging current of a 24V/500Ah battery bank: 50A to
100A.
The temperature sensor supplied automatically adjusts the charging voltage
to the battery temperature.
If faster charging – and a subsequent higher current – is required:
- the temperature sensor supplied should be fitted to the battery, since fast
charging can lead to a considerable temperature rise of the battery bank. The
charging voltage is adapted to the higher temperature (i.e. lowered) by means
of the temperature sensor.
- the bulk charging time will sometimes be so short that a fixed absorption
time would be more satisfactory ('fixed' absorption time, see ds5, step 2).
Procedure
The battery charging current can be set in four steps, using DIP switches ds4
and ds3 (default setting: 75%).
ds4 ds3
off
off = 25%
off
on = 50%
on
off = 75%
on
on = 100%

5.5.1.4 Stand-alone, parallel, 2-3 phase operation

DIP switches ds2 and ds1 are reserved for the selection of stand-alone,
parallel, split phase or 3-phase operation
34
off = 15A (1.8kVA at 120V)
on = 20A (2.4kVA at 120V)
off = 25A (3.0kVA at 120V)
on = 30A (3.6kVA at 120V)
off = 35A (4.2kVA at 120V)
on = 40A (4.8kVA at 120V)
off = 50A (6.0kVA at 120V)
on = 60A (7.2kVA at 120V)