Control plug-in modules

8
Control plug-in modules
8.1

E3L020 'I/O' control plug-in module

Item
Component
1
'S3' programming switch: I bus ad-
dress
2
'S2' service switch: Activate test LEDs
'H1'....'H16'
8.2

E3L030 'VdS' control plug-in module

Item
Component
1
'S3' programming switch: I bus ad-
dress
0 ς resistor 'X12': Configure LED4
2
3
'R191' resistor: For SST
Bridges
X2/16 -> 18
X2/15 -> 17
22
Building Technologies
Fire Safety
Preparation
Set in accordance with system documentation
Set to 'ON' for commissioning
1
S3
S2
2
Preparation
Set in accordance with system documentation
Use if LED4 (reserve/FBF) is to light up in 'degraded
mode operation'
Remove (or change), if an external
extinguishing system is connected which
needs a different value.
In accordance with VdS guideline 2540 (Oct 2008),
SST is no longer permitted via E3L030.
2
X12
R191
S3
1
H1
H16
3
Default ex factory
Address 0
To 'OFF'
Default ex factory
Address 0
Not used
3K32 used