Preparations; Programming The System - Siemens AlgoRex CS1140 Comissioning Hardware

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

3.1.1

Preparations

3.2

Programming the system

Building Technologies
Fire Safety
Compact control panel CI1145 –> see document 008727
κ
Fit and connect the hardware
Control panel CC/CI
κ
according to system documentation:
Fit power supply unit
Connect mains cable and supply line
Fit board holder and attach connection cable
Set I bus address on all plug-in modules / set switches and bridges
Possibly, insert RAM and EPROMs on central plug-in module, operating ter-
minal and C bus gateway
Insert all plug-in modules
Attach I bus flat cable and 5 V/24 V supply cable via all I bus plug-in modules
Connect fire controls
Connect batteries
Operating terminal CT11
κ
Remove shielding hood, insert RAM and EPROMs, or possibly load other
Flash program file
Set bridges
Slide in designation strip
Connect C bus and supply line according to system document
Fit terminal
Plain text display terminal and plain text operating terminal
κ
Set LON bus address / set switch
Possibly remove resistor
Parallel display, 'Extinguishing' operating unit
κ
Set device address / possibly remove resistor array
Switching on for the first time
Establish mains voltage, note safety regulations in chapter 2
For start-up procedure –> see page 39
For programming the system –> refer to AlgoWorks online help.
Commissioning overview
11
008726_e_en_--
06.2017