E3X102/103 Control Panel Module - Siemens AlgoRex CS1140 Comissioning Hardware

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

CPUs
5.2

E3X102/103 control panel module

Item
Component
1
SRAM
2
Flash ROM
3
'S2' programming switch: Battery type
selection
4
'S3' programming switch: 'Battery
charging part' I bus address
5
'S4' switch: Service functions
6
'S5' programming switch: Service and
horn functions
7
Bridge 'X61': 'Remote alarm' contact
assignment
8
'X60' bridge: 'Control panel' ground
fault monitoring
9
'X30' bridge: Ground fault monitoring
'C bus'
10
'R178/179' 'R196'...'R199' resistors: C
bus impedance
14
Building Technologies
Fire Safety
Preparation
Set to battery make used, see description in docu-
ment 001260
Set in accordance with system documentation
For 'S4-9' commissioning, set to 'ON': –> red test
LEDs ('H2'...'H7') active
Set according to description in document 001260
Resolder if 'Normally closed contact (NC)' is needed
For ground fault monitoring –> see page 37
Set according to description in document 001260,
'Programming ground fault monitoring' chapter
Adjust if necessary
1
SRAM
2
6
S5
S4
5
7
8
X60
X61
Flash-ROM
R1xx
X30
S3
S2
3
4
Default ex factory
E3X102 (2x512Kx8 bits)
E3X103 (4x512Kx8 bits)
Program file
E3X102 CCX00xxx
E3X103 CCY00xxx
'ALARMCOM (FIAMM)' type
Address 0
All switches to 'OFF'
All switches to 'OFF'
To '2-3' ('Normally open contact
(NO)')
Removed (inactive)
To 'J1' (not monitored)
Used for 110 ς impedance
(G51)
X15
X16
X17
10
9
008726_e_en_--
06.2017