13

Gateway

13.1

E3H020 C bus gateway

Item
Component
1
RAM modules 'D11/12', 'D15/16' or
RAM kit Z3S070 (2x 512Kx8 bits)
2
Select EPROM kit
CKQ00xxx (2x 512Kx8 bits) or
CKW00xxx (2x 512Kx8 bits)
3
'S3' programming switch:
C bus address
4
'S5' programming switch:
Select interface path
5
Resistors 'R180/183'
'R173/174/177/178': C bus impedance
0 ς resistors 'X15'....'X18': Program-
6
ming of terminal strip 'X1–17...20'
Building Technologies
Fire Safety
Take measures to protect against overvoltage when inserting RAM and
NOTE
EPROMs. Press modules all the way into the base.
Preparation
Change RAM if necessary, see description in docu-
ment 001260
Insert (note positions for 'ODD' and 'EVEN')
Set in accordance with system documentation
Set according to system documentation, see also
description in document 001260
Adjust if necessary
Resolder if gateway with autonomous supply is used,
see description in document 001260
For communication module K1H022, modems K1D..., modem filter module
M3P030, see document 1062
For NK823x Ethernet port, see document A6V10062437
Gateway
Default ex factory
4x512Kx8 bits
Not used
Address 0
To 'OFF'
Used for 110 ς impedance
(G51)
To 'X15'.....'X18' ('CK' + supply
from control panel)
008726_e_en_--