K3I110 Lon I/O Board; B3Q580 Plain Text Display Terminal - Siemens AlgoRex CS1140 Comissioning Hardware

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

Operation and floor repeater display
11.8

K3I110 LON I/O board

Item
Component
1
'S3' programming switch: LON bus
address
2
'X30' bridge: Ground fault monitoring
'Inputs'
3
'R1' resistor: 'LON bus' terminator
resistor
4
Bridge 'X39': Relay test
5
'X21' bridge: Activate test LEDs
'H1'....'H16'
11.9

B3Q580 plain text display terminal

Item
Component
1
'S3' programming switch: LON bus
address
2
'S4-1' programming switch: Buzzer off
3
'R1' resistor: 'LON bus' terminator
resistor
4
Designation strips included in kit
Z5B710...750
30
Building Technologies
Fire Safety
Preparation
Set in accordance with system documentation
Set according to system documentation, see also
description in document 001260
When using stub line: If K3I110 is not the last device,
remove resistor 'R1', also see description in document
001260
Set to 'left' for test –> all relays approved, also see
description in document 001260
Set to 'left' for commissioning, also see description in
document 001260
4
5
X39
X21
X30
S3
R1
Then connect data bus and LON bus cable, supply cable as well as peripherals
and fit.
Preparation
Set in accordance with system documentation
For 'S4-1' commissioning, set to 'ON'
When using stub line: If B3Q5xx is not the last de-
vice, remove resistor 'R1', also see description in
document 001260
Slide in
S4
R1
3
Then connect LON bus and supply cable, for installation –> see document
001260.
2
H1
1
H16
3
2
S3
1
4
Default ex factory
Address 0
To 'right' (not monitored)
100 ς used
To 'right' (all relays blocked)
To 'right' (service LEDs deac-
tivated)
Default ex factory
Address 0
To 'OFF'
100 ς used
Please order separately, or
produce yourself with DOT
Word templates (document
006516)
008726_e_en_--
06.2017