Technical Details; Operating Manual - Pilz PSS Series Operating Manual

Programmable safety control
Hide thumbs Also See for PSS Series:
Table of Contents

Advertisement

Available languages

Available languages

PSS PS230

Technical Details

Elektrical Data
Supply Voltage
Tolerance Range
Frequency Range
Output Voltage
Power Consumption
Switch-on Current
Operation
Battery
Service Life
Environmental Data
Protection type (EN 60 529, 10/91)
Protection class (DIN VDE 0106,
Part 1/A1, 04/90)
Mounting position
Ambient temperature (DIN IEC 68-2-14, 06/87) 0 ... 60 °C
Storage temperature (EN 60 068-2-1/-2, 03/93) -25 ... +70 °C
Relative humidity
(DIN IEC 68-2-30, 09/86)
Condensation
Vibration (EN 60 068-2-6, 04/95)
Shock (DIN IEC 68-2-29)
EMC
Mechanical Data
Weight
The names of products, goods and technologies are trademarks of the companies concerned.
4
120 V AC/230 V AC, switches automatically
-15 ... +10 %
48 ... 62 Hz
5.0 V DC/max. constant load: 10 A
12 V DC/ 0.25 A
short-circuit protected, current-limited
80 VA
10 A (15 A when warm)
SMPS
Type: Lithium 3.6 V, Size AA
Approx. 2 years
IP20 (installed on module rack)
1 (installed on module rack)
Vertical on module rack
Max. 95 % r.h.
Not permitted
Frequency range: 10 ... 100 Hz
Amplitude: 0.1 mm, max. 5g
30g, 11 ms/10g, 16 ms
EN 50 082-2, 03/95
EN 55 011 A, 03/91
1640 g

Operating Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pss ps230

Table of Contents