General Settings - Gabarron Ecombi HHR Series Installation Instructions Manual

Smart storage heater
Hide thumbs Also See for Ecombi HHR Series:
Table of Contents

Advertisement

Installation Instructions

General Settings

The General settings MUST be configured after
installation by the installer to ensure correct operation.
It is important to configure the off peak times correctly.
The HHR allows you to configure two separate off peak
charge periods; Period 1 via P01 & P02 and Period 2
via P03 & P04. If you only have one charge period then
set P03 and P04 to 00:00.
To enter the general settings menu turn ON the heater
via the switch at the right side of the heater while
holding down the moon button at the same time. ST will
be displayed, at this point you can release the moon
button.
Use the
and
menu options.
To look or change each setting, press and release the
moon button and then use the
buttons to adjust. Press the
The default settings are as follows:-
ST
: Initial % of storage charge
P01 : Start time of off peak period 1
P02 : End time of off peak period 1
P03 : Start time of off peak period 2
P04 : End time of off peak period 2
P05 : Ambient sensor offset ±5°C
P06 : Max. working hours of balancing element : 5
P07 : Over temperature protection °C
P08 : Display temp. Centigrade or Fahrenheit : °C
Open : Open window detection option
To skip through P05, P06, P07, P08 and Open options
simply press and release the plus button until you exit
back to displaying the temperature.
8
buttons to move down and up the
and
moon button to set.
: 80
: 00:00
: 07:00
: 00:00
: 00:00
: 0.0
: 2
: Off