Call Up Table Of Contents - GEA Grasso Manual

System control standard package with piston compressors single stage and two stage
Table of Contents

Advertisement

Grasso
Refrigeration Division
1.2.3

Call up table of contents

To get to the table of contents, press the
Number
Title
05
Actual values
10
Control settings
15
Operating modes
20
Limit values
25
Alarms
30
Timer settings
35
Unit Options
50
Configuration
90
Main system menu
To get to these menus, position the cursor on the menu name (using the
the
key.
Parameter changes in menu 20, 30, 35, 50 can cause serious damage to the piston compressor unit!
1.2.3.1
Actual values menu
05 Actual values
PV
SP
Cap
Imot
Tc
dPoil
Actual values 01 >>
Capacity
(
)
Suction press
Discharge press
<<
Actual values 01 >>
Oil diff press
Oil press
Crankc press
<<
Actual values 01
Chap. 1 - 6
key. A list of the available menus is then displayed.
Help text
Display of all unit's actual values
Display and set up of all control parameters
Selection of operation mode
Set up of alarm, warning and limitation parameters
Display of current and previous alarms
Set up of timers
Selection of unit option menus
Enter:
- Compressor type
- Scaling of the sensors
PV:
SP:
Cap:
Imot:
Tc:
dPoil:
Capacity:
Suction press:
Discharge press:
Oil diff press:
Oil press:
>>
Crankc press:
638660E_chapter1.doc
- Refrigerant used
- With/without economiser
- Number of cylinders
Process Variable, display in °C/R (pressure) or °C (temp)
Set Point display in °C / °C/R
Actual capacity step (for the low pressure stage) in %
Motor current in A
Discharge pressure in °C/R
Differential oil pressure in bar
Actual capacity step for the high and low pressure stage
in %
Suction pressure in bar (a)
Discharge pressure in bar (a)
Oil differential pressure in bar, calculated from the oil
pressure minus crankcase or suction pressure
Oil pressure in bar (a)
Crankcase pressure in bar (a)
GRASSO SYSTEM CONTROL
or
key) and confirm with
01.2004/1