GEA Grasso Manual page 161

System control standard package with piston compressors single stage and two stage
Table of Contents

Advertisement

Grasso
Refrigeration Division
#
Title
50
Configuration
Sensor scaling:
Discharge pressure
Begin (4mA)
End (20mA)
Sensor scaling:
Itermediate pressure
Begin (4mA)
End (20mA)
Sensor scaling:
Oil pressure
Begin (4mA)
End (20mA)
Sensor scaling:
Crankcase pressure
Begin (4mA)
End (20mA)
Sensor scaling:
Suction temperature
Sensor scaling:
Discharge temperature
Sensor scaling:
Intermediate temperature LP
01.2003/ 0
Unit
HotKey
DIR
Sensor:
bar (a)
bar (a)
Sensor:
bar (a)
bar (a)
Sensor:
bar (a)
bar (a)
Sensor:
bar (a)
bar (a)
Sensor:
Offset (K)
°C
Spann (%)
°C
Sensor:
Offset (K)
°C
Spann (%)
°C
Sensor:
Offset (K)
°C
Spann (%)
°C
638660E_chapter9.doc
GRASSO SYSTEM CONTROL
Parameters for configuration values
Range
Default setting
Disch press
0,0 ... 40,0
0,0 ... 40,0
Interm press
0,0 ... 40,0
0,0 ... 40,0
Oil press
0,0 ... 40,0
0,0 ... 40,0
Crankc press
0,0 ... 40,0
0,0 ... 40,0
Suction temp
-10,0 ... 10,0
-20,0 ... 20,0
Disch temp
-10,0 ... 10,0
-20,0 ... 20,0
Intm temp LP
-10,0 ... 10,0
-20,0 ... 20,0
Project setting
0,0
25,0
0,0
25,0
0,0
25,0
0,0
10,0
0,0
0,0
0,0
0,0
0,0
0,0
Kap.9 - 5

Advertisement

Table of Contents
loading