GEA Grasso Manual page 40

System control standard package with piston compressors single stage and two stage
Table of Contents

Advertisement

Grasso
Refrigeration Division
2.4
Start up sequence
2.4.1
Single stage and booster piston compressor packages
Starting conditions fulfilled
Output — compressor motor on
Feedback — compressor motor on equals 1
'Motor feedback' timer active
Release of capacity control system
Booster pressure reached
A
Single stage:
B
Booster:
If
(1) Starting conditions fulfilled
Then
(2) Set output — compressor motor on
Then
(4) Start 'Motor feedback' timer
Then
(5) Set unloaded start
(3) Feedback — compressor motor equals 1
If
Then
(4) Stop 'Motor feedback' timer
If
(5) Unloaded start ended
Then
(6) Release of capacity control system
or
(5) Unloaded start ended
If
and
(7) Booster pressure reached
Then
(6) Release of capacity control system
Chap. 2 - 4
Unloaded start
Release of capacity control system after unloaded start.
Release of capacity control system after that the booster pressure is reached.
638660E_chapter2.doc
Figure 2.4,
Start up sequence for single stage (A) and booster (B) piston
compressor package
GRASSO SYSTEM CONTROL