GEA Grasso Manual page 53

System control standard package with piston compressors single stage and two stage
Table of Contents

Advertisement

Grasso
Refrigeration Division
2.7.2.6
Low and high suction pressure alarm
Both low and high suction pressures are monitored. In case the suction pressure becomes too low or too high an
alarm is generated. Both alarms do not become active until the start up process has been completed. After
starting the compressor motor an additional delay time of 5 minutes becomes active for the high suction
pressure alarm only. During this time the suction pressure is allowed to exceed its maximum limit.
The low suction pressure alarm function is illustrated in the following diagram.
P
Suction pressure
suc
A..
Time characteristic of the suction
pressure
V..
Forced reduction of the capacity
due too low suction pressure
B..
Low suction pressure limitation
active
T..
Limit timer active; After that this
timer has expired the capacity
control is enabled again and the
compressor capacity can be
increased.
b..
Limit value for disabling capacity
increase
f..
Limit value for forced reduction of
capacity
W..
Warning limit
Al..
Alarm limit
ML W.. Warning active
ML A.. Alarm active
3..
Reset of the active alarm
Suction press
Psuc low alarm
Low warning
+
Limit values 01
01.2004/1
Figure 2.21, Low suction pressure alarm
Suction pressure: Actual suction pressure in bar (a)
Psuc low alarm:
Warning:
>>
638660E_chapter2.doc
Alarm limit for minimum suction pressure in bar (a)
Enter the warning value as an offset to the alarm limit in
bar
GRASSO SYSTEM CONTROL
Chap. 2 - 17