Parameters Display - Baxi LUNA 3 COMFORT AIR Series Installers And Users Instructions

High efficiency wall-mounted gas-fired boilers
Hide thumbs Also See for LUNA 3 COMFORT AIR Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 39
19.1 information and advanced setting mode
To access the Information and Advanced Setting mode, it is necessary to press, for at least 3 seconds, the ip button; in
INFO mode the display shows "inFo".
To escape the INFO mode briefly press the ip button. In this mode press the oK button to scroll the windows; to set
parameters press the +/-
WarninG
Communications between the main board and the remote control is not immediately. In some case it may hap-
pen that the command given through the remote control takes some time depending on the type of the tran-
sferred information.
central heating (ch)
"ch Sl"
Max. heating circuit setpoint, value settable with the buttons +/-
WarninG: to change the unit of measure from °C to °F and vice versa, press the
"eXt°c"
Outside temperature (with external sensor connected).
"ch o>"
Maximum Heating flow temperature.
"ch r<"
return heating temperature (unplanned).
"ch s^"
CH temperature setpoint.
"ch MX"
Maximum CH temperature setpoint (max. settable value).
"ch Mn"
Minimum CH temperature setpoint (min. settable value).
DoMestic hot Water (D.h.W.)
• "hW o>" D.H.W. flow temperature.
• "hW s^ " Maximum setpoint temperature value setting. Press the +/-
• "hW MX" Maximum D.H.W. temperature setpoint (max. settable value).
• "hW Mn" Minimum D.H.W. temperature setpoint (min. settable value).
aDvanceD inForMation
• "pWr %" Power level/modulating flame (%).
• "p Bar"
Water pressure heating circuit (bar).
• "f l/m"
Water flow rate (l/min).
• "eXt°c"
External temperature (°C)
paraMeters settinG
• "K reG" Central Heating setting constant (0,5...6,5 - factory setting 3 - refer to section 25 - Graph 3).
Press +/-
buttons to set the value. An high value setting involves a high flow temperature. To set a correct value
of the Central Heating constant K REG, involves the room temperature to match the CH setpoint with external tem-
perature changes over.
• "BuilD" A parameter that takes into account the degree of building insulation (1..10 - factory setting 5). When the
outside temperature varies, the room temperature changes at different rates, depending on the building thermal sto-
rage capacity. An high value setting involves a heavy building structures (the room temperature will respond slower
to outside temperature variations; buildings with thick walls or with external insulation). A low value setting involves
a light building structures (the room temperature will respond quicker to outside temperature variations; buildings
with a light envelope).
Press +/-
buttons to set the value.
• "ySelf" CH flow temperature auto setting function Enabled/Disabled (1/0). Factory setting 1. With function enable,
the constant "K reG" is modified to match the room temperature comfort. This function operates with the external
sensor connected.
Press +/-
buttons to set the value.
• "aMBon" room temperature influence Enabled/Disabled (1/0). Factory setting 1. In this case, the rooms tempera-
ture regulation it depends on the flow temperature set ("CH SL").
Press +/-
buttons to set the value.
note: refer to the summary table of possible amBon and moDul combinations.
inStructionS Pertaining to the inStaller

19. parameters display

button.
buttons to set the value.
62
.
button.
926.427.1
- GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Luna 3 comfort air 310 fiLuna 3 comfort air 250 fi

Table of Contents