Termination - Leuze electronic DDLS 200 Technical Description

Bus-capable optical data transmission
Hide thumbs Also See for DDLS 200:
Table of Contents

Advertisement

DeviceNet / CANopen

9.4.1 Termination

DeviceNet
• External termination for M12 connector version is available as an option (see chapter 9.2)
• Resistance and other features are described in the DeviceNet specifications of the ODVA (Open
DeviceNet Vendor Association).
CANopen
• Value: typically 120Ω (included with the device, mounted between CAN_L and CAN_H)
• External termination for M12 connector version is available as an option
• Resistance and other features are described in the CANopen specification ISO 11898.
Power
Ω
Termination with 120
DeviceNet/CANopen
incoming bus
Figure 9.10: Termination in the unit.
A 120Ω resistor is connected standard between terminals CAN_L and CAN_H. If the device is not the
last subscriber of the bus segment, the resistor must be removed and the outgoing bus cable connect-
ed to the terminal strip.
Leuze electronic
DDLS 200
43