9.1

Mechanical stability in operation

The switch meets the following requirements for mechanical stability:
IEC 60068-2-6 (vibration)
● Securing on a DIN rail
5 – 9 Hz: 3.5 mm
9 – 150 Hz: 1 g
1 octave/min, 20 sweeps
IEC 60068-2-27 (shock)
● Securing on a DIN rail
15 g, 11 ms duration, 6 shocks per axis
Installation guidelines
The devices meet the requirements if you adhere to the installation and safety instructions
contained in this documentation and in the following documentation when installing and
operating the devices.
● "Industrial Ethernet / PROFINET Industrial Ethernet" System Manual
support.industry.siemens.com/cs/ww/en/view/27069465)
● "Industrial Ethernet / PROFINET - Passive Network Components" System Manual
support.industry.siemens.com/cs/ww/en/view/84922825)
● "EMC Installation Guidelines" configuration manual
cs/ww/en/view/60612658)
Personal injury and property damage can occur
The installation of expansions that are not approved for SIMATIC NET products or their target
systems may violate the requirements and regulations for safety and electromagnetic
compatibility.
Only use expansions that are approved for the system.
Note
The test was performed with a device and a connected communications partner that also meets
the requirements of the standards listed above.
When operating the device with a communications partner that does not comply with these
standards, adherence to the corresponding values cannot be guaranteed.